A. Features
1.Automatic compensation function. It can be automatically compensated to improve the reliability of the smoke detector, such as external environment (temperature, humidity, dust, static, etc.) factors caused by changes in performance drift.
2.Built-in product ID code
3.Intelligent judgment, cleaning forecast function
4.Two bus, linkage, nonpolarity
5.Advanced electronic coding technology, improving coding flexibility
6.Two response modes (commonly referred to as algorithms)
Mode 1: Fast response mode. In this mode, the detector will alarm when the smoke concentration exceeds the alarm threshold more than 3 times consecutively. This mode applies to the system debugging installation phase or test phase.
Mode 2: Intelligent response mode. It is conducive to accurately determine the fire alarm signal, reduce false alarm (factory default).
B. Specifications
1.Working voltage:15-28V Impulse voltage
2.Working current:
1)Standby current:≤0.5mA
2)Alarm current:≤2.8mA
3.Type:Addressable, 2 wire(nonpolarity)
4.Encoding: Electronic code
5.Work indication:
1)Normal monitoring status :LED light will blink periodically
2)Fire status: Remain lit
3)Failure status: LED light remain off or blink irregularly
6.Operating environment: Temperature-10℃~50℃, Relative humidity≤95%RH No condensation
7.Color: white
8.Weight:120g
9. Executive standard:GB 4715-2005
c. Installation
1. Smoke detector installation and wiring diagram shown in Figure 2
Figure 2 S-6001 Installation diagram
86H50 standard embedded box can be used as pre-embedded box; when installation, locate smoke detector on the base and rotate clockwise.
2. Wiring requirements: Wire should be RVS-2 * 1.0 mm
2 or 1.5 mm
2
3.
WARNING: Before installing the smoke detector, turn off the power and make sure that all the bases are installed securely.
E. Use and operation
Encoding operation: you can use our company's hand-held encoder P-6010 to live coding. When encoding, connect the two clips of the encoder to the two terminals of the linkage, open the handheld encoder power, enter the address code to be written (address code range must be: 1-242, the address code for the same loop is unique). Press the "write code" button, if encoding is successful, the encoder will display the address number after sending the address code. If failed, the encoder will display “FAL” after sending the address code.
For details on the steps and methods of encoding, refer to the "P-6010 Handheld Encoder User's Manual".
F. Note
1. The plastic part attached with smoke detector is dust cover. Please cover the dust cover after the installation or room decoration, painting construction, so that the smoke detectors are contaminated.
2. The alarm function test of smoke detector should be performed every six months.
3. When the controller detects the cleaning forecast, please send the number of smoke detectors back to the company for cleaning, in order to avoid false or false positives, resulting in unnecessary losses.
4. Equipment transportation, handling, storage must be carried out in the packaging state, gently loading and unloading, to prevent damage to the collision. Storage environment should be kept ventilated, dry, avoid open storage.