Supplier Info.
Report Item
Your report on Product(s) will be sent to EC21 Administrators once submitted.
Then, Administrators will investigate and then take appropriate actions.
Contact Supplier
PAC-F100 is multifunction relay that have all functions, protection, control and monitoring. This relay is available by backup protection, control and monitoring of distribution line, transmission line and transformer irrelatively to grounded system(earthed network, unearthed network and resistance earthed network etc.) of system, and to distribution power-system because has directional detection element applicable. PAC-F100 has various measuring and monitoring function such as quantity of electricity measure, self-diagnosis, current input circuit monitoring, current/voltage unbalance monitoring, PT fuse monitoring and Trip Circuit Supervision (TCS). PAC-F100 has four setting groups for protection, and change and apply setting group according to system driving condition change and enables optimum protection. This relay can be various and designs economically trip logic, inter-lock sequence and lock-out function without external addition logic or connection by programmable logic(Easy-Logic). Event and waveform recording function of PAC-F100 offer driving history of necessary data and device to fault analysis. PAC-F100 has event and waveform recording data that is stored even if control power is lost. Stored recording can analyze in PC after upload using front communication port in integration PC program (PACManagerTM). If min/max value is inputted through analog input, MIN/MAX recording function of PAC-F100 is recorded quantity of electricity by primary value with inputted time, and recording is kept even if control power is lost. PAC-F100 has 8 basic LEDs and 8 user setting LEDs, and offers convenient menu-tree through graphic LCD, and relay and circuit breaker can be controlled by keypad. There is one RS-232 port on front of PAC-F100 that can communicate with PC program (PACManagerTM), and are two RS-485 ports on rear of PAC-F100 can connect with remote monitoring system. This relay provides ModBus, DNP3.0 and IEC 60870-5-103 protocol for communication with remote monitoring system.
Features
- Digital line Protective Relay that use two processors
- Use possibility by backup protection, control and monitoring of distribution line, transmission line
and transformer
- 4 protection element setting groups
- Eighteen protection element : OCR, OCGR, SGR, Thermal Overload, UCR, NSOCR, UBOCR, OVR,
UVR, OVGR, NSOVR, FREQ, AREL, CBF, PHS DIR, GND DIR, COLD LD, INRUSH
- Various TC curves : IEC standard, ANSI standard, KEPCO induction type, P&C curve
- Control of CB open/close on local and remote mode
- Metering : 3-phase current/voltage, Sequence current/voltage, 3 phase real /reactive /apparent
power, Energy, Frequency, Power factor, Thermal, THD(Total Harmonic Distortion) and harmonic
size (to 31 harmonic waves), Demand current, Three phase demand real/reactive/apparent
power, Reclosing count
- Event recording upto 1024 and maximum 8 fault waveform recording (64 samples/cycles)
- Quantity of electricity MIN/MAX recording : Line to line voltage, Voltage/current by a phase, Three
phase real/reactive/apparent power, Three phase power factor, Demand current by a phase,
Three phase demand real/reactive/apparent power, Frequency
- Engineering tool : Setting change, Event inquiry, Fault waveform analysis
- Graphic LCD (240 ´ 128, 16line ´ 30character) : Single line diagram, tree structure menu, 16
LEDs, 11 Keypad button
- Communication port : Front interface RS232 1 port (ModBus Protocol : Setting change,
Event/Fault waveform transmission, measuring monitor), Rear interface RS485 2 ports (SCADA
communication, DNP3.0/ModBus/IEC60870- 5-103 protocol)
- Self-diagnosis function : DC power supply, Memory, CPU, Setting range, DSP, A/D converter,
Analog input circuit, inside logic element and digital input/output circuit
- Five monitoring functions : PT Fuse failure monitoring(PT Fuse failure), Current input circuit
monitoring(Current Sum), Voltage unbalance monitoring(Voltage Balance), Current unbalance
monitoring(Current Balance), Trip circuit (TCS) monitoring function
- Eight user setting LEDs
- Panel design easiness in sequence logic structure through EasyLogic Editor
- Test function : Output relay and front display department
- Software upgrade easiness by flash memory use
- Flexible control source (option : AC 110 ~ 240 V, DC 19 ~ 130 V)
- Access Security by password for settings and CB control
Registration Date | 2002/03/13(Year/Month/Date) |
---|---|
Buyer / Seller in EC21 | Seller |
Business Type | Manufacturer |
Year established | 1999 |
Employees total | 51 - 100 |
Annual revenue | USD 10,000,001 - 50,000,000 |
Company | PNC Technologies Co., Ltd. |
---|---|
Address | 5F, Kwangmyong B/D, 115-3, Bangi-dongSongpa-kuSeoul138-050Korea |
Phone | 82 - 2 - 22408107 |
Fax | 82 - 2 - 22408188 |
Homepage | http://www.pnctech.co.kr |
Contact | Eunji Park / OverseasSalesAssistantManager |